4.Digital Echo ProcessingVarious digital,statistically based, processing techniquesare employed to render the Level Genie immune to random noiseinputs

Seite 3

IV.INSTALLATION1.Electronic PackageThe electronic circuits of the Level Genie UltrasonicLevel Switch are contained on a single printed circuitmotherbo

Seite 4

5.Alarm Anti-Latch Circuit (stab select at A position)In some applications,the Level Genie is used to detectan object instead of a material level.Usua

Seite 5

disable the alarm time delays while calibrating.The"10 ft. - 5 ft.'"toggle should be in the appropriateposition reflecting the desired

Seite 6

d.within the vessel such as a supporting beam which wouldinterfere with the sound path between the transducer andthe material being measured.NOTEUltra

Seite 7

V.CALIBRATIONBefore applying line powerto the Level Genie, ensure thatall pre-start-up checks (Section IV) have been completed.1.General Alarm Calibra

Seite 8

9.h.i.j.SPECIFIC CALIBRATION OF HI-HI PROGRAM MODULE(OMIT IF OTHER PROGRAM USED)With the transducer placed at a distance from a fixedtarget representa

Seite 9

a delay in output response by 3 seconds or 10 secondsdepending on the position of the delay toggle.IMPORTANTRotating the"NEAR"and"FAR&q

Seite 10

2.Pump Up/Down Program Module----rActuationIn "pump down" operation,the liquid level must rise abovethe NEAR setpoint to de-energize the rel

Seite 11

c.Set the "NEAR" potentiometer 1/4 turn from fully counterclockwise.a.Set the"FAR" potentiometer fully clockwise.This setsthe trip

Seite 13

VI.MISCELLANEOUSChecks to make before pushing the Panic ButtonSYMPTOMCAUSEUnable to calibrate oneProgram module offset in socketsetpoint or inverted.H

Seite 14

VII.MAINTENANCEThis equipment requires very little maintenance dueto its solid-state circuitry.However,a program ofperiodic preventive maintenance sho

Seite 15

FIG-1 OUTLINE & MOUNTING DIAGRAM

Seite 17

FIG:3 EASILY AVOIDABLE INSTALLATION ERRORS.

Seite 23

CONTENTSSECTIONIIIIIIIVVVIVIIFIG.5b TRANSDUCER DO'S AND DON'TSFIG. 1FIG. 2FIG. 3FIG. 4FIG. 5FIG. 6FIG. 7TITLEGENERAL INFORMATIONSPEICIF

Seite 24

a company to be controlled byThroughout the world Milltronics has become a namerespected for the high quality of its industrial process controls.The e

Seite 25

I.GENERAL INFORMATIONThe Milltronics Level Genie Ultrasonic System is an entirely"Solid State Package",designed to provide contact closure a

Seite 26

II.Power RequiredTransducerRangeoutputSet PointsSet Point HysterisisResponse TimeTime DelayRepeatabilityTemperature EffectsTemperature RangeSeparation

Seite 27

Operating Modes*EnclosureWeight1.Pump up/down2.Hi-Lo alarm3.Hi-Hi alarm4.Lo-Lo alarmOne programming module suppliedwith unit.Additional modulesavailab

Seite 28

III.THEORY OF OPERATIONTRANSCEIVER CIRCUITRY1.General DescriptionThe transceiver uses a single tuning section which istime-shared between the transmit

Seite 29

Q6 and Q7 provide additional amplification. Q7 alsoserves as a detector charging C9 with the positive half-cycles of the received signal.Q8 is turned

Seite 30

ECHO PROCESSING LOGIC1.General DescriptionThe digital echo processor establishes the necessarytiming and limit functions. Coincidently, statisticaltec